District Heating Leakage Protection System UMS-F

Principle

District Heating Leak Protection system UMS-F employs values of volume flow from two pulsing flow meters calculated regularly.

Two monitoring functions are employed with the fetched volume flow data for protecting the installation from leakage, as the UMS-F closes the cut-off valves when a leak is detected by any monitor.


 

System Diagram UMS-F

Logging

Alarm and Event log
UMS-F maintains a log of the most recent 250 events, such as Power Down, Power Up, Alarm and Error messages, Alarm Acknowledge and Autoreset, External Control Input change, State change and Sequence execution.

 

Jumper Log
UMS-F maintains a log of the 15 most recent changes to the jumper settings.

These logs serve to document events surrounding actual incidents in the installation.

spacer

Table valid for UMS-F with Kamstrup ULTRAFLOW®54 Flow Meters

System Capacity and head loss Dimensions
Nom. Kap.
qp (m³/h)
 ΣΔp@qp Equivalent
Kv (m³/h)
(mwc) (kPa) Flow meter Valve Check Valve
UMS-F0,6-MK2 0,6 0,86 8,6 2,1 G¾B x 110 mm (R½) ½" x 77 mm ½" x 48 mm
UMS-F1,5-MK2 1,5 3,5 35 2,6 G¾B x 110 mm (R½) ½" x 77 mm ½" x 48 mm
UMS-F2,5-MK2 2,5 3,1 31 4,5 G1B x 190 mm (R¾) ¾" x 77 mm ¾" x 53mm
UMS-F3,5-MK2 3,5 2,3 23 7,4 G5/4B x 260 mm (R1) 1" x 90 mm 1" x 59 mm
UMS-F6-MK2 6 4,6 46 8,8 G5/4B x 260 mm (R1) 1¼" x 110 mm 1¼" x 66 mm
UMS-F10-MK2 10 2,4 24 20 G2B x 300 mm (R1½) 1½" x 120 mm 1½" x 71 mm
UMS-F10F-MK2 10 2,4 24 20 DN40 x 300 mm 1½" x 120 mm 1½" x 71 mm
UMS-F15-MK2 15 3,8 38 24 DN50 x 270 mm 2" x 140 mm 2" x 80 mm
UMS-F25-MK2 25 2,4 24 51 DN65 x 300 mm DN65 x 46 mm DN65 x 54 mm
UMS-F40-MK2 40 2,1 21 88 DN80 x 300 mm DN80 x 46 mm DN80 x 57 mm
UMS-F60-MK2 60 1,3 13 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
UMS-F100-MK2 100 3,5 35 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
UMS-F150-MK2 150 0,83 8,3 519 DN150 x 500 mm DN150 x 56 mm DN150 x 76 mm
spacer
page 1

Guidelines for Installation