|
It should be noted that part of the TV-technical equipment is critical, and the network
will suffer blackout if the cooling system fails for just half an hour - provided no
action is taken to rectify the situation.
Substantial amounts of energy are used in the former cattle auction. The TV2 headquarters
consume over 4 MWh of electrical energy annually, a major part of which is used for cooling
purposes in the summer. Outdoor climate is helping in the winter, where part of the cooling
system idles as a consequence.
A pipe fractured - no water damage resulted
The cooling system is used for indoor conditioning as well as for cooling technical equipment.
The cooling medium used is plain water, which feeds radiators in the ventilation system that
provides an air inlet temperature between 17 and 21 °C. Condensers are mounted on the roof,
where outside air cools the freon of the closed cooling circuit.
All in all 18 ventilation systems are humming in the former cattle market, and a while ago
frostbite fractured a radiator in a section housing part of the TV technical installations.
Nothing happened, however, thanks to the DanTaet leakage protection system, which was originally
installed when the network moved in sixteen years ago.
- Of course a little water escaped, as the system is so large. From detection of the leakage
until the valves are fully closed some water will inevitably escape in larger systems, but
the damage is limited and contained by the protection system, explains Poul Erik Schultz.
- In large systems, subdivision into several smaller protected circuits is a good idea, and
we have this under consideration. We also employ other protection strategies; in another
section we use a heat exchanger, from which only the water from the secondary side may
escape in case of frostbite damage.
Possible distributed leakage protection
TV2 is used to fractures in pipes and radiators. They average five a year, caused by a combination
of frostbite and corrosion, and the fractures typically occur in the bend preceding the next loop.
- We watch the installations more closely now, knowing what may happen, Poul Erik Schultz emphasises.
The added watchfulness has made leakage protection more relevant than ever, and as a further
consequence, the original DanTaet system was replaced in 2003 with a brand new and more capable
system sporting a modem via which the manufacturer DanTaet a/s may check system functionality
and integrity at all times. The protection system is mounted in the district heating installation
in the compound technical building, and consists of a control unit, two flow meters and two
electrically actuated valves in the forward and return flow pipes.
|