Cooling Circuit Leakage Protection system KMP-K
Kamstrup

Principle

Cooling Circuit Leakage Protection system KMP-K employs values of volume flow from two flow meters, which are fetched regularly via a digital interface from a Kamstrup MULTICAL®602, 801, or 6M2 energy meter to which the flow meters are attached.

Two monitoring functions are employed with the fetched flow data for protecting the installation from leakagem as the KMP-K closes the cut-off valves when a leak is detected by any monitor.

Component errors reported in the heat meters's INFO code are propagated by the KMP-K as System Fault alarm.

system diagram KMP-K

Logging

Alarm and Event log

KMP-K maintains a log over the most recent 250 events. Events include power down/up, alarm and error reports, acknowledgements and autoreset, key input, control input and sequencer action.

Jumper log

KMP-K maintains a log of the 15 most recent changes to the internal jumper setting.

These logs contribute to clarification and documentation of actual events.

spacer
System
K6A (K8A)
Capacity and Pressure Loss Dimensions
Nom. Cap.
qp (m³/h)
 ΣΔp@qp Equivalent
Kv (m³/h)
(mwc) (kPa) Flow Meter Valve Check Valve
KMP-K6A1,5 1,5 3,5 35 2,6 G¾B x 110 mm (R½) ½" x 77 mm ½" x 48 mm
KMP-K6A2,5 2,5 3,1 31 4,5 G1B x 190 mm (R¾) ¾" x 77 mm ¾" x 53 mm
KMP-K6A3,5 3,5 2,3 23 7,4 G5/4B x 260 mm (R1) 1" x 90 mm 1" x 59 mm
KMP-K6A6 6 4,6 46 8,8 G5/4B x 260 mm (R1) 1¼" x 110 mm 1¼" x 66 mm
KMP-K6A10 10 2,4 24 20 G2B x 300 mm (R1½) 1½" x 120 mm 1½" x 71 mm
KMP-K6A10F 10 2,4 24 20 DN40 x 300 mm 1½" x 120 mm 1½" x 71 mm
KMP-K6A15 15 3,8 38 24 DN50 x 270 mm 2" x 140 mm 2" x 80 mm
KMP-K6A25 25 2,4 24 51 DN65 x 300 mm DN65 x 46 mm DN65 x 54 mm
KMP-K6A40 40 2,1 21 88 DN80 x 300 mm DN80 x 46 mm DN80 x 57 mm
KMP-K6A60 60 1,3 13 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
KMP-K6A100 100 3,5 35 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
KMP-K6A150 150 0,83 8,3 519 DN150 x 500 mm DN150 x 56 mm DN150 x 76 mm
KMP-K6A400 400 1,2 12 1162 DN200 x 500 mm DN200 x 60 mm DN200 x 95 mm
KMP-K6A600 600 1,2 12 1723 DN250 x 600 mm DN250 x 68 mm DN250 x 108 mm
KMP-K6A1000 1000 1,3 13 2779 DN250 x 600 mm DN300 x 78 mm DN300 x 143 mm
spacer

KMP-K8I and KMP-K6M

Flow meters and valves are selected for each system individually according to media type and operating conditions; hence there are no general system tables for these families.

Variants

Variant -M2 is a complete new delivery.
Variants -M1 and -M0 are used with an existing Kamstrup cooling meter.
Note an existing cooling meter must be mains supplied for use with KMP-K.

Delivery KMP-K

 

Variant (suffix) -M2 -M1 -M0
KMP-K control unit 1 1 1
Cut-off valves 2 2 2
Check valve 1 1 1
MULTICAL®calculator 1 0 0
Flow meters 2 1 0
Data module (KMP-K6A/K6M) 1 1 1